COMMISSION REGULATION (EU) 2015/1095
of 5 May 2015
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process chillers
(Text with EEA relevance)
Article 1
Subject matter and scope
Article 2
Definitions
Article 3
Ecodesign requirements and timetable
Article 4
Conformity assessment
Article 5
Verification procedure for market surveillance purposes
Article 6
Indicative benchmarks
Article 7
Review
Article 8
Entry into force
ANNEX I
Definitions applicable for Annexes II to XII
Definitions related to professional refrigerated storage cabinets and blast cabinets
Definitions related to condensing units
Definitions related to process chillers
Common definitions:
ANNEX II
Ecodesign requirements for professional refrigerated storage cabinets and blast cabinets
1. REQUIREMENTS FOR ENERGY EFFICIENCY
2. REQUIREMENTS FOR PRODUCT INFORMATION
| 
                               Model(s): [information identifying the model(s) to which the information relates]  | 
                        |||||
| 
                               Intended use  | 
                           
                               storage  | 
                        ||||
| 
                               Operating temperature(s)  | 
                           
                               chilled/frozen/multi-use  | 
                        ||||
| 
                               Category  | 
                           
                               Vertical/counter  | 
                        ||||
| 
                               (where applicable) Heavy-duty/light-duty  | 
                        |||||
| 
                               Refrigerant fluid(s): [information to identify the refrigerant fluid(s), including GWP]  | 
                        |||||
| 
                               Item  | 
                           
                               Symbol  | 
                           
                               Value  | 
                           
                               Unit  | 
                        ||
| 
                               Annual Energy Consumption  | 
                           
                               AEC  | 
                           
                               x,xx  | 
                           
                               kWh  | 
                        ||
| 
                               Energy Efficiency Index  | 
                           
                               EEI  | 
                           
                               x,xx  | 
                           
                               
  | 
                        ||
| 
                               Net volume  | 
                           
                               VN  | 
                           
                               x,x  | 
                           
                               litre  | 
                        ||
| 
                               (where applicable)  | 
                           
                               
  | 
                           
                               
  | 
                           
                               
  | 
                        ||
| 
                               Chilled volume  | 
                           
                               VNRef  | 
                           
                               x,x  | 
                           
                               litre  | 
                        ||
| 
                               Frozen volume  | 
                           
                               VNFrz  | 
                           
                               x,x  | 
                           
                               litre  | 
                        ||
| 
                               Refrigerant charge  | 
                           
                               
  | 
                           
                               x,xx  | 
                           
                               kg  | 
                        ||
| 
                               Contact details  | 
                           
                               Name and address of the manufacturer or its authorised representative.  | 
                        ||||
ANNEX III
Method for calculating the energy efficiency index for professional refrigerated storage cabinets
| 
                   Category  | 
               
                   Value for M  | 
               
                   Value for N  | 
            
| 
                   Vertical Chilled  | 
               
                   1,643  | 
               
                   609  | 
            
| 
                   Vertical Frozen  | 
               
                   4,928  | 
               
                   1 472  | 
            
| 
                   Counter Chilled  | 
               
                   2,555  | 
               
                   1 790  | 
            
| 
                   Counter Frozen  | 
               
                   5,840  | 
               
                   2 380  | 
            
ANNEX IV
Measurements and calculations for professional refrigerated storage cabinets
| 
                               Test room climate class  | 
                           
                               Dry bulb temperature, °C  | 
                           
                               Relative humidity, %  | 
                           
                               Dew point, °C  | 
                           
                               Water vapour mass in dry air, g/kg  | 
                        
| 
                               3  | 
                           
                               25  | 
                           
                               60  | 
                           
                               16,7  | 
                           
                               12,0  | 
                        
| 
                               4  | 
                           
                               30  | 
                           
                               55  | 
                           
                               20,0  | 
                           
                               14,8  | 
                        
| 
                               5  | 
                           
                               40  | 
                           
                               40  | 
                           
                               23,9  | 
                           
                               18,8  | 
                        
ANNEX V
Ecodesign requirements for condensing units
1. REQUIREMENTS FOR ENERGY EFFICIENCY
| 
                               Operating temperature  | 
                           
                               Rated capacity PA  | 
                           
                               Applicable ratio  | 
                           
                               Value  | 
                        
| 
                               Medium  | 
                           
                               0,2 kW≤ PA ≤ 1 kW  | 
                           
                               COP  | 
                           
                               1,20  | 
                        
| 
                               1 kW< PA ≤ 5 kW  | 
                           
                               COP  | 
                           
                               1,40  | 
                        |
| 
                               5 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               2,25  | 
                        |
| 
                               20 kW < PA ≤ 50 kW  | 
                           
                               SEPR  | 
                           
                               2,35  | 
                        |
| 
                               Low  | 
                           
                               0,1 kW≤ PA ≤ 0,4 kW  | 
                           
                               COP  | 
                           
                               0,75  | 
                        
| 
                               0,4 kW< PA ≤ 2 kW  | 
                           
                               COP  | 
                           
                               0,85  | 
                        |
| 
                               2 kW < PA ≤ 8kW  | 
                           
                               SEPR  | 
                           
                               1,50  | 
                        |
| 
                               8 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               1,60  | 
                        
| 
                               Operating temperature  | 
                           
                               Rated capacity PA  | 
                           
                               Applicable ratio  | 
                           
                               Value  | 
                        
| 
                               Medium  | 
                           
                               0,2 kW≤ PA ≤ 1kW  | 
                           
                               COP  | 
                           
                               1,40  | 
                        
| 
                               1 kW< PA ≤ 5 kW  | 
                           
                               COP  | 
                           
                               1,60  | 
                        |
| 
                               5 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               2,55  | 
                        |
| 
                               20 kW < PA ≤ 50 kW  | 
                           
                               SEPR  | 
                           
                               2,65  | 
                        |
| 
                               Low  | 
                           
                               0,1 kW≤ PA ≤ 0,4 kW  | 
                           
                               COP  | 
                           
                               0,80  | 
                        
| 
                               0,4 kW< PA ≤ 2 kW  | 
                           
                               COP  | 
                           
                               0,95  | 
                        |
| 
                               2 kW < PA ≤ 8 kW  | 
                           
                               SEPR  | 
                           
                               1,60  | 
                        |
| 
                               8 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               1,70  | 
                        
2. REQUIREMENTS FOR PRODUCT INFORMATION
| 
                   Model(s): [information identifying the model(s) to which the information relates]  | 
            ||||||
| 
                   Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit]  | 
            ||||||
| 
                   Item  | 
               
                   Symbol  | 
               
                   Value  | 
               
                   Unit  | 
            |||
| 
                   Evaporating temperature (1)  | 
               
                   t  | 
               
                   – 10 °C  | 
               
                   – 35 °C  | 
               
                   °C  | 
            ||
| 
                   Parameters at full load and ambient temperature 32 °C  | 
            ||||||
| 
                   Rated cooling capacity  | 
               
                   PA  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   Rated power input  | 
               
                   DA  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   Rated COP  | 
               
                   COPA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Parameters at full load and ambient temperature 25 °C  | 
            ||||||
| 
                   Cooling capacity  | 
               
                   P2  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   Power input  | 
               
                   D2  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   COP  | 
               
                   COP2  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Parameters at full load and ambient temperature 43 °C (where applicable)  | 
            ||||||
| 
                   Cooling capacity  | 
               
                   P3  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   Power input  | 
               
                   D3  | 
               
                   x,xxx  | 
               
                   x,xxx  | 
               
                   kW  | 
            ||
| 
                   COP  | 
               
                   COP3  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Other items  | 
            ||||||
| 
                   Capacity control  | 
               
                   fixed/step/variable  | 
            |||||
| 
                   Contact details  | 
               
                   Name and address of the manufacturer or its authorised representative.  | 
            |||||
| 
                   Model(s): [information identifying the model(s) to which the information relates]  | 
            |||||
| 
                   Refrigerant fluid(s): [information to identify the refrigerant fluid(s) intended to be used with the condensing unit]  | 
            |||||
| 
                   Item  | 
               
                   Symbol  | 
               
                   Value  | 
               
                   Unit  | 
            ||
| 
                   Evaporating temperature (2)  | 
               
                   t  | 
               
                   – 10 °C  | 
               
                   – 35 °C  | 
               
                   °C  | 
            |
| 
                   Annual electricity consumption  | 
               
                   Q  | 
               
                   x  | 
               
                   x  | 
               
                   kWh/a  | 
            |
| 
                   Seasonal energy performance ratio  | 
               
                   SEPR  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Parameters at full load and ambient temperature 32 °C (point (A)  | 
            |||||
| 
                   Rated cooling capacity  | 
               
                   PA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Rated power input  | 
               
                   DA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Rated COP  | 
               
                   COPA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Parameters at part load and ambient temperature 25 °C (point (B)  | 
            |||||
| 
                   Declared cooling capacity  | 
               
                   PB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared power input  | 
               
                   DB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared COP  | 
               
                   COPB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Parameters at part load and ambient temperature 15 °C (point (C)  | 
            |||||
| 
                   Declared cooling capacity  | 
               
                   Pc  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared power input  | 
               
                   Dc  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared COP  | 
               
                   COPC  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Parameters at part load and ambient temperature 5 °C (point (D)  | 
            |||||
| 
                   Declared cooling capacity  | 
               
                   PD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared power input  | 
               
                   DD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared COP  | 
               
                   COPD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Parameters at full load and ambient temperature 43 °C (where applicable)  | 
            |||||
| 
                   Cooling capacity  | 
               
                   P3  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Power input  | 
               
                   D3  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            |
| 
                   Declared COP  | 
               
                   COP3  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            |
| 
                   Other items  | 
            |||||
| 
                   Capacity control  | 
               
                   fixed/step/variable  | 
            ||||
| 
                   Degradation coefficient for fixed and staged capacity units  | 
               
                   Cdc  | 
               
                   0,25  | 
               
                   
  | 
            ||
| 
                   Contact details  | 
               
                   Name and address of the manufacturer or its authorised representative.  | 
            ||||
ANNEX VI
Measurements and calculations for condensing units
| 
                   j  | 
               
                   Tj  | 
               
                   hj  | 
            
| 
                   1  | 
               
                   – 19  | 
               
                   0,08  | 
            
| 
                   2  | 
               
                   – 18  | 
               
                   0,41  | 
            
| 
                   3  | 
               
                   – 17  | 
               
                   0,65  | 
            
| 
                   4  | 
               
                   – 16  | 
               
                   1,05  | 
            
| 
                   5  | 
               
                   – 15  | 
               
                   1,74  | 
            
| 
                   6  | 
               
                   – 14  | 
               
                   2,98  | 
            
| 
                   7  | 
               
                   – 13  | 
               
                   3,79  | 
            
| 
                   8  | 
               
                   – 12  | 
               
                   5,69  | 
            
| 
                   9  | 
               
                   – 11  | 
               
                   8,94  | 
            
| 
                   10  | 
               
                   – 10  | 
               
                   11,81  | 
            
| 
                   11  | 
               
                   – 9  | 
               
                   17,29  | 
            
| 
                   12  | 
               
                   – 8  | 
               
                   20,02  | 
            
| 
                   13  | 
               
                   – 7  | 
               
                   28,73  | 
            
| 
                   14  | 
               
                   – 6  | 
               
                   39,71  | 
            
| 
                   15  | 
               
                   – 5  | 
               
                   56,61  | 
            
| 
                   16  | 
               
                   – 4  | 
               
                   76,36  | 
            
| 
                   17  | 
               
                   – 3  | 
               
                   106,07  | 
            
| 
                   18  | 
               
                   – 2  | 
               
                   153,22  | 
            
| 
                   19  | 
               
                   – 1  | 
               
                   203,41  | 
            
| 
                   20  | 
               
                   0  | 
               
                   247,98  | 
            
| 
                   21  | 
               
                   1  | 
               
                   282,01  | 
            
| 
                   22  | 
               
                   2  | 
               
                   275,91  | 
            
| 
                   23  | 
               
                   3  | 
               
                   300,61  | 
            
| 
                   24  | 
               
                   4  | 
               
                   310,77  | 
            
| 
                   25  | 
               
                   5  | 
               
                   336,48  | 
            
| 
                   26  | 
               
                   6  | 
               
                   350,48  | 
            
| 
                   27  | 
               
                   7  | 
               
                   363,49  | 
            
| 
                   28  | 
               
                   8  | 
               
                   368,91  | 
            
| 
                   29  | 
               
                   9  | 
               
                   371,63  | 
            
| 
                   30  | 
               
                   10  | 
               
                   377,32  | 
            
| 
                   31  | 
               
                   11  | 
               
                   376,53  | 
            
| 
                   32  | 
               
                   12  | 
               
                   386,42  | 
            
| 
                   33  | 
               
                   13  | 
               
                   389,84  | 
            
| 
                   34  | 
               
                   14  | 
               
                   384,45  | 
            
| 
                   35  | 
               
                   15  | 
               
                   370,45  | 
            
| 
                   36  | 
               
                   16  | 
               
                   344,96  | 
            
| 
                   37  | 
               
                   17  | 
               
                   328,02  | 
            
| 
                   38  | 
               
                   18  | 
               
                   305,36  | 
            
| 
                   39  | 
               
                   19  | 
               
                   261,87  | 
            
| 
                   40  | 
               
                   20  | 
               
                   223,90  | 
            
| 
                   41  | 
               
                   21  | 
               
                   196,31  | 
            
| 
                   42  | 
               
                   22  | 
               
                   163,04  | 
            
| 
                   43  | 
               
                   23  | 
               
                   141,78  | 
            
| 
                   44  | 
               
                   24  | 
               
                   121,93  | 
            
| 
                   45  | 
               
                   25  | 
               
                   104,46  | 
            
| 
                   46  | 
               
                   26  | 
               
                   85,77  | 
            
| 
                   47  | 
               
                   27  | 
               
                   71,54  | 
            
| 
                   48  | 
               
                   28  | 
               
                   56,57  | 
            
| 
                   49  | 
               
                   29  | 
               
                   43,35  | 
            
| 
                   50  | 
               
                   30  | 
               
                   31,02  | 
            
| 
                   51  | 
               
                   31  | 
               
                   20,21  | 
            
| 
                   52  | 
               
                   32  | 
               
                   11,85  | 
            
| 
                   53  | 
               
                   33  | 
               
                   8,17  | 
            
| 
                   54  | 
               
                   34  | 
               
                   3,83  | 
            
| 
                   55  | 
               
                   35  | 
               
                   2,09  | 
            
| 
                   56  | 
               
                   36  | 
               
                   1,21  | 
            
| 
                   57  | 
               
                   37  | 
               
                   0,52  | 
            
| 
                   58  | 
               
                   38  | 
               
                   0,40  | 
            
ANNEX VII
Ecodesign requirements for process chillers
1. REQUIREMENTS FOR ENERGY EFFICIENCY
| 
                               Heat transfer medium at the condensing side  | 
                           
                               Operating temperature  | 
                           
                               Rated cooling capacity PA  | 
                           
                               Minimum SEPR value  | 
                        
| 
                               Air  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               2,24  | 
                        
| 
                               PA > 300 kW  | 
                           
                               2,80  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               1,48  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               1,60  | 
                        ||
| 
                               Water  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               2,86  | 
                        
| 
                               PA > 300 kW  | 
                           
                               3,80  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               1,82  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               2,10  | 
                        
| 
                               Heat transfer medium at the condensing side  | 
                           
                               Operating temperature  | 
                           
                               Rated cooling capacity PA  | 
                           
                               Minimum SEPR value  | 
                        
| 
                               Air  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               2,58  | 
                        
| 
                               PA > 300 kW  | 
                           
                               3,22  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               1,70  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               1,84  | 
                        ||
| 
                               Water  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               3,29  | 
                        
| 
                               PA > 300 kW  | 
                           
                               4,37  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               2,09  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               2,42  | 
                        
2. REQUIREMENTS FOR PRODUCT INFORMATION
| 
                   Model(s): [information identifying the model(s) to which the information relates]  | 
            ||||||
| 
                   Type of condensing: [air-cooled/water-cooled]  | 
            ||||||
| 
                   Refrigerant fluid(s): [information identifying the refrigerant fluid(s) intended to be used with the process chiller]  | 
            ||||||
| 
                   Item  | 
               
                   Symbol  | 
               
                   Value  | 
               
                   Unit  | 
            |||
| 
                   Operating temperature  | 
               
                   t  | 
               
                   – 8 °C  | 
               
                   – 25 °C  | 
               
                   °C  | 
            ||
| 
                   Seasonal Energy Performance Ratio  | 
               
                   SEPR  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Annual electricity consumption  | 
               
                   Q  | 
               
                   x  | 
               
                   x  | 
               
                   kWh/a  | 
            ||
| 
                   Parameters at full load and reference ambient temperature (point (A)  | 
            ||||||
| 
                   Rated cooling capacity  | 
               
                   PA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Rated power input  | 
               
                   DA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Rated EER  | 
               
                   EERA  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Parameters at rating point B  | 
            ||||||
| 
                   Declared cooling capacity  | 
               
                   PB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared power input  | 
               
                   DB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared EER  | 
               
                   EERB  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Parameters at rating point C  | 
            ||||||
| 
                   Declared cooling capacity  | 
               
                   Pc  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared power input  | 
               
                   Dc  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared EER  | 
               
                   EERC  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Parameters at rating point D  | 
            ||||||
| 
                   Declared cooling capacity  | 
               
                   PD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared power input  | 
               
                   DD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   kW  | 
            ||
| 
                   Declared EER  | 
               
                   EERD  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Other items  | 
            ||||||
| 
                   Capacity control  | 
               
                   
  | 
               
                   fixed/staged(2)/variable  | 
            ||||
| 
                   Degradation coefficient for fixed and staged capacity units(1)  | 
               
                   Cc  | 
               
                   x,xx  | 
               
                   x,xx  | 
               
                   
  | 
            ||
| 
                   Contact details  | 
               
                   Name and address of the manufacturer or its authorised representative.  | 
            |||||
ANNEX VIII
Measurements and calculations for process chillers
ANNEX IX
Verification procedure for market surveillance purposes for professional refrigerated storage cabinets
ANNEX X
Verification procedure for market surveillance purposes for condensing units
ANNEX XI
Verification procedure for market surveillance purposes for process chillers
ANNEX XII
Indicative benchmarks referred to in Article 6
| 
                               
  | 
                           
                               Net volume (litres)  | 
                           
                               Annual energy consumption  | 
                           
                               EEI  | 
                        
| 
                               Chilled vertical  | 
                           
                               600  | 
                           
                               474,5  | 
                           
                               29,7  | 
                        
| 
                               Chilled counter  | 
                           
                               300  | 
                           
                               547,5  | 
                           
                               21,4  | 
                        
| 
                               Frozen vertical  | 
                           
                               600  | 
                           
                               1 825  | 
                           
                               41,2  | 
                        
| 
                               Frozen counter  | 
                           
                               200  | 
                           
                               1 460  | 
                           
                               41,0  | 
                        
| 
                               Operating temperature  | 
                           
                               Rated capacity PA  | 
                           
                               Applicable ratio  | 
                           
                               Benchmark value  | 
                        
| 
                               Medium  | 
                           
                               0,2 kW ≤ PA ≤ 1 kW  | 
                           
                               COP  | 
                           
                               1,9  | 
                        
| 
                               1 kW < PA ≤ 5 kW  | 
                           
                               COP  | 
                           
                               2,3  | 
                        |
| 
                               5 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               3,6  | 
                        |
| 
                               20 kW < PA ≤ 50 kW  | 
                           
                               SEPR  | 
                           
                               3,5  | 
                        |
| 
                               Low  | 
                           
                               0,1 kW ≤ PA ≤ 0,4 kW  | 
                           
                               COP  | 
                           
                               1,0  | 
                        
| 
                               0,4 kW < PA ≤ 2 kW  | 
                           
                               COP  | 
                           
                               1,3  | 
                        |
| 
                               2 kW < PA ≤ 8 kW  | 
                           
                               SEPR  | 
                           
                               2,0  | 
                        |
| 
                               8 kW < PA ≤ 20 kW  | 
                           
                               SEPR  | 
                           
                               2,0  | 
                        
| 
                               Heat transfer medium at the condensing side  | 
                           
                               Operating temperature  | 
                           
                               Rated cooling capacity PA  | 
                           
                               Minimum SEPR value  | 
                        
| 
                               Air  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               3,4  | 
                        
| 
                               PA > 300 kW  | 
                           
                               3,7  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               1,9  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               1,95  | 
                        ||
| 
                               Water  | 
                           
                               Medium  | 
                           
                               PA ≤ 300 kW  | 
                           
                               4,3  | 
                        
| 
                               PA > 300 kW  | 
                           
                               4,5  | 
                        ||
| 
                               Low  | 
                           
                               PA ≤ 200 kW  | 
                           
                               2,3  | 
                        |
| 
                               PA > 200 kW  | 
                           
                               2,7  |