COMMISSION REGULATION (EU) No 1253/2014
of 7 July 2014
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for ventilation units
(Text with EEA relevance)
Article 1
Subject matter and scope
Article 2
Definitions
Article 3
Ecodesign requirements
Article 4
Information requirements
Article 5
Conformity assessment
Article 6
Verification procedure for market surveillance purposes
Article 7
Benchmarks
Article 8
Review
Article 9
Entry into force
ANNEX I
Definitions
ANNEX II
Specific ecodesign requirements for RVUs, as referred to in Article 3(1) and 3(3)
ANNEX III
Specific ecodesign requirements for NRVUs, as referred to in Article 3(2) and 3(4)
ANNEX IV
Information requirements for RVUs as referred to in Article 4(1)
ANNEX V
Information requirements for NRVUs as referred to in Article 4(2)
ANNEX VI
Verification procedure for market surveillance purposes
|
Parameter |
Verification tolerances |
|
SPI |
The measured value shall be no more than 1,07 times the maximum declared value. |
|
Thermal efficiency RVU and NRVU |
The measured value shall be no less than 0,93 times the minimum declared value. |
|
SFPint |
The measured value shall be no more than 1,07 times the maximum declared value. |
|
Fan efficiency UVU, non-residential |
The measured value shall be no less than 0,93 times the minimum declared value. |
|
Sound power level RVU |
The measured value shall be no more than the maximum declared value plus 2 dB. |
|
Sound power level NRVU |
The measured value shall be no more than the maximum declared value plus 5 dB. |
ANNEX VII
Benchmarks
ANNEX VIII
Calculation of the specific energy consumption requirement
|
general typology |
MISC |
||||
|
Ducted units |
1,1 |
||||
|
Non-ducted units |
1,21 |
||||
|
ventilation control |
CTRL |
||||
|
Manual control (no DCV) |
1 |
||||
|
Clock control (no DCV) |
0,95 |
||||
|
Central demand control |
0,85 |
||||
|
Local demand control |
0,65 |
||||
|
motor & drive |
x-value |
||||
|
on/off & single speed |
1 |
||||
|
2-speed |
1,2 |
||||
|
multi-speed |
1,5 |
||||
|
variable speed |
2 |
||||
|
Climate |
th in h |
ΔΤh in K |
tdefr in h |
ΔΤdefr in K |
Qdefr (*1) in kWh/a.m2 |
|
Cold |
6 552 |
14,5 |
1 003 |
5,2 |
5,82 |
|
Average |
5 112 |
9,5 |
168 |
2,4 |
0,45 |
|
Warm |
4 392 |
5 |
— |
— |
— |
|
Defaults |
value |
||||
|
specific heat capacity of air, cair in kWh/(m3K) |
0,000344 |
||||
|
net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 |
1,3 |
||||
|
reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 |
2,2 |
||||
|
annual operating hours, ta in h |
8760 |
||||
|
primary energy factor electric power generation & distribution, pef |
2,5 |
||||
|
space heating efficiency, ηh |
75 % |
||||